Das, Goutam and Ghosh Chowdhury, S and Ray, Ashok K and Das, Swapan K and Bhattacharya, D K (2002) Failure of a super heater tube. Engineering Failure Analysis, 9 (5). pp. 563-570.
PDF - Published Version Restricted to NML users only. Others may use -> 337Kb |
Abstract
The failure of two adjacent platen super heater tubes of a thermal power plant has been analysed. One tube fractured with a fish mouth opening and another thinned down considerably. A significant amount of oxide layer was observed in the inner side of the failed tube. In the other tube the inner oxide layer was very small and the tube was thinned down due to fireside corrosion. The unexposed tube from the same lot revealed a ferritic bainitic microstructure. The failed tube also showed a ferrite bainite microstructure but most of the bainitic carbide had transformed to globular form. Considerable carbide precipitation both in grain boundary (GB) and inside grains were observed. A large number of cavities and micro-cracks were observed along the grain boundaries. A similar microstructure was observed on the same tube 10 cm away from the failed region. The micrograph at the fracture location showed a similar microstructure but the grains are very much elongated. The formation of globular oxide on the other tube was compared to that of the failed tube. Due to breakage of oxide scale of the failed tube, the metal surface of the failed tube was exposed to steam at a higher temperature and this accelerated the oxide growth. This led to creep damage of the material. Ultimately, failure occurred due to rapid overheating of the tube material.
Item Type: | Article |
---|---|
Official URL/DOI: | http://dx.doi.org/10.1016/S1350-6307(01)00040-1 |
Uncontrolled Keywords: | Super heater tube; Corrosion; Failure analysis; Creep; Oxidation |
Divisions: | Material Science and Technology |
ID Code: | 286 |
Deposited By: | INVALID USER |
Deposited On: | 19 Nov 2009 09:51 |
Last Modified: | 14 Dec 2011 12:58 |
Related URLs: |
Repository Staff Only: item control page